High-efficiency in-line pump with EC motor of energy efficiency class IE5 in accordance with IEC 60034-30-2, hydraulics with minimum efficiency index MEI ≥ 0.7 and electronic power adjustment with a glanded pump design. The pump is configured as a single-stage low-pressure centrifugal pump with flange connection and mechanical seal. The Stratos GIGA2.0-D has been predominantly designed for pumping heating water (acc. to VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, air-conditioning and cooling systems.
Design:
– Single-stage low-pressure centrifugal pump with one-piece shaft in monobloc design
– Spiral housing in in-line design (suction and discharge ports with the same flanges in a line)
– PN 16 flange – in accordance with EN 1092-2
– Pressure measuring connections (R 1/8) for mounted differential pressure sensor (version …-R1 without differential pressure sensor)
– Pump housing and motor flange with cataphoretic coating as standard
– Mechanical seal for pumping water up to Tmax. = +140 °C. A glycol admixture of 20 % to +40 % by volume is permitted up to T ≤ +40 °C. An alternative mechanical seal must be provided in water-glycol mixtures with glycol proportions > 40 % up to max. 50 % by volume and a fluid temperature of > +40 °C up to max. +120 °C or fluids other than water. When using water-glycol mixtures, the use of an S1 variant with a corresponding mechanical seal is generally recommended.
– Connection voltages:
– 3~440 V +-10% 50/60 Hz; 3~400 V +-10% 50/60 Hz; 3~380 V -5% +10% 50/60 Hz
– Version M-: 1~220 V – 240 V (+-10%), 50/60 Hz
– Compliance with electromagnetic compatibility without additional measures
– Interference emission for residential environment according to EN 61800-3:2018
– Interference immunity for industrial environments according to EN 61800-3:2018
Control modes:
– Permanent, automatic power adjustment to system requirements without setpoint specification Wilo Dynamic Adapt plus (factory setting).
– Constant temperature (T-const.)
– Constant differential temperature (dT-const.)
– Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple secondary pumps (Multi-Flow Adaptation).
– Constant volume flow (Q-const.)
– Variable differential pressure (dp-v) with the option to set the nominal duty point Q and H
– Constant differential pressure (dp-c)
– Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator)
– Constant speed (n-const.)
– User-defined PID control
Functions:
– Selection of the field of application in the setting assistant
– Heat quantity measurement
– Cooling quantity measurement
– Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.)
– Operating modes of twin-head pump: Main/standby operation, efficiency-optimised parallel operation for dp-c and dp-v
– Pump automatically deactivates when no flow is detected (No-Flow Stop)
– Switchover between heating and cooling mode (automatic, external or manual)
– Ability to save and restore configured pump settings (3 restoration points)
– Display of current duty point in the hydraulic duty chart
– Correction of viscous fluids via adjustment of viscosity and density
– Fault and warning messages shown in plain text with advice on resolving the issue
– Integrated full motor protection
Display in the “Home screen” of the graphic display:
– Control mode currently set
– Current setpoint
– Current volume flow (only if a differential pressure sensor is connected)
– Current fluid temperature (only if temperature sensor is connected)
– Current power consumption
– Cumulative electric consumption
Version:
– 4 configurable analogue inputs: 0-10 V, 2-10 V, 0-20 mA, 4-20 mA and commercially available PT1000 (only on two analogue inputs); +24 V DC power supply
– 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
– 2 configurable signal relays for run signals and fault messages
– Slot for Wilo-CIF modules with interfaces for building automation (BA) (optional accessories: CIF modules Modbus RTU, BACnet MS/TP, LON, PLR, CAN)
– Wilo Net as a Wilo system bus for communication between Wilo products, e.g. Multi-Flow Adaptation; dual-pump operation
– Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
– Rotatable, graphic colour display (4.3 inches) with one button manual operation level
– Bluetooth interface via Wilo-Smart Connect module BT
– Use the Wilo-Assistant app to read and set operating data and –among other things– set up a commissioning protocol through the Bluetooth interface
– Integrated dual-pump management (twin-head pumps are prewired) when using 2 single pumps as two-pump unit (connection via Wilo Net)
– Cable break detection when using an analogue signal (in connection with 2 – 10 V or 4 – 20 mA)
– Time stamp for error/warnings and historical operating data
– Continuous operating data memory
– Standard condensate drainage holes in the motor housing (closed upon delivery)
– Air vent valve on the lantern
Scope of delivery:
– Pump
– Wilo-Smart Connect module BT
– Threaded cable glands with sealing inserts
– Installation and operating instructions and declaration of conformity
Accessories must be ordered separately:
3 mounting brackets with fixation material for installation on a base
– Blind flanges for twin-head pump housing
– Installation aid for mechanical seal (incl. mounting bolts)
– For connection to building automation:
– CIF module PLR
– CIF module LON
– CIF module BACnet MS/TP
– CIF module Modbus RTU
– CIF module CANopen
– CIF module Ethernet Multi-protocol (Modbus TCP, BACnet/IP)
– Connection M12 RJ45 CIF Ethernet
– Differential pressure sensor DPS 2 … 10 V
– Differential pressure sensor DPS 4 … 20 mA
– Temperature sensor PT1000 AA
– Sensor sleeves for the installation of temperature sensors in the pipe
Operating Data
Fluid media: Water 100 %
Fluid temperature: 20.00 °C
Requested flow:
Requested head:
Min. fluid temperature: -20 °C
Max. fluid temperature: 140 °C
Min. ambient temperature: 0 °C
Max. ambient temperature: 50 °C
Maximum operating pressure: 16 bar
Note on dimensioning:
Minimum efficiency index (MEI): ≥ 0.7
Drive
Mains connection: 1~230V/50 Hz
Motor efficiency class: IE5
Power consumption: 1,600 W
Rated power: 1.5 kW
Max current: 7.6 A
Max. speed: 3,450 1/min
Emitted interference: EN 61800-3
Interference resistance: EN 61800-3
Insulation class: F
Protection class motor: IP55
Motor protection: PTC integrated
Materials
Pump housing: 5.1301/EN-GJL-250
Impeller: PPS-GF40
Shaft: 1.4057
Shaft seal: AQ1EGG
Lantern: 5.1301, EN-GJL-250 cataphoretic-coated
Installation dimensions
Pipe connection on the suction side: DN 40, PN 16
Pipe connection on the discharge side: DN 40, PN 16
Port-to-port length: 280 mm
Ordering information
Brand: Wilo
Product description: Stratos GIGA2.0-D 40/1-23/M-1,5
Net weight, approx.: 75 kg
Article number: 2207130