Hydro EN 65-250 /263 T2JS A-U2-B

SKU: 99844232 Categories: Pumps , Hydro EN
Product name Hydro EN 65-250 /263 T2JS A-U2-B
Product No 99844232
EAN number 5713835086860
Rated flow 128.5 m³/h
Rated head 80.8 m
Diesel cooling flow 3 m³/h
Nominal impeller diameter 250 mm
Approvals CE
Fire standard EN 12845
Maximum allowed back pressure 9.80 kPa
Number of pumps 3
Backup pumps 1
Main pump type NKF 65-250/263
Number of diesel driven pumps 2
Jockey pump type CM3-13
Number of Jockey pumps 1
Pump housing Cast iron
Impeller Bronze
Manifold Galvanized steel
Range of ambient temperature 10 .. 40 °C
Relative humidity 50 %
Maximum operating pressure 16 bar
Type of inlet connection DIN
Type of outlet connection DIN
Size of inlet connection DN 80
Size of outlet connection DN 100
Type of inlet connection for Jockey pump Rp
Size of inlet connection for Jockey pump 1 1/4 inch
Earth connection PE
Elevation above sea level 300 m
Pumped liquid Water
Liquid temperature range 0 .. 40 °C
Selected liquid temperature 20 °C
Density 998.2 kg/m³
Motor standard IEC
Driver type Diesel engine
Mains frequency 50 Hz
Motor nominal speed (w/o slip) 2950 rpm
Enclosure class (IEC 34-5) IP54
Motor standard for Jockey pump IEC
Mains supply for jockey motor 3 x 400 V
Rated power – P2 for Jockey pump 2.2 kW
Rated current for Jockey pump 4.6 A
Number of poles for Jockey pump 2
Method of start for Jockey pump Direct-on-line (DOL)
Mains supply for diesel motor 1 x 230 V
Engine gross power NB 53 kW
Engine continuous power NA 48.2 kW
Battery 12 V
Engine cooling type Heat exchanger cooled
Exhaust flow 595 m³/h
Engine aspiration Turbocharged
Heat radiation 8200 kcal/h
Maximum exhaust temperature 628 °C
Net weight 1510 kg
Gross weight 1740 kg

Request a quote

Or send us an email to info@waterials.com

    Scroll to Top