Premium smart-pump Wilo-Stratos MAXO
High-efficiency in-line glandless pump with EC motor and electronic power adjustment. Can be used for chilled water, heating water and water/glycol mixtures. Energy efficiency index (EEI) between ≤ 0.17 and ≤ 0.19 depending on pump type.
Control modes:
– Permanent, automatic performance adjustment according to system requirements without setpoint specification Wilo Dynamic Adapt plus (factory setting). Up to 20% energy savings compared to dp-v control mode.
– Constant temperature (T-const.)
– Constant differential temperature (dT-const.)
– Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation).
– Constant volume flow (Q-const.)
– Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator)
– Constant differential pressure (dp-c)
– Variable differential pressure (dp-v) with the option to set the nominal duty point
– Constant speed (n-const.)
– User-defined PID control
Functions:
– Heat quantity measurement
– Cooling quantity measurement
– Pump automatically deactivates when no flow is detected (No-Flow Stop)
– Switchover between heating and cooling mode (automatic, external or manual)
– Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.)
– Dual-pump operations: Efficiency-optimised parallel operation for dp-c and dp-v, main and standby operation
– Ability to save and restore configured pump settings (3 restoration points)
– Fault and warning messages shown in plain text with advice on resolving the issue
– Pump venting function for automatic venting of the rotor chamber
– Automatic night setback
– Automatic deblocking function and integrated full motor protection
– Dry-running detection
Display:
– Control mode
– Setpoint
– Volume flow
– Temperature
– Power consumption
– Electric consumption
– Active influences (e.g. STOP, No-Flow Stop)
Version:
– 2 configurable analogue inputs: 0–10 V, 2–10 V, 0–20 mA, 4–20 mA and commercially available PT1000; +24 V DC power supply
– 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
– 2 configurable signal relays for run signals and fault messages
– Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
– Wilo Net as a Wilo system bus for communication between Wilo products, e.g. Multi-Flow Adaptation; dual-pump operation and Wilo-Smart Gateway
– Integrated temperature sensor
– Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
– Graphic colour display (4.3 inches) with one-button manual operation
– Use the Wilo-Assistant app to read and set operating data and –among other things– set up a commissioning protocol through the Bluetooth interface (no further accessories required)
– Integrated dual-pump management (twin-head pumps are prewired) when using 2 single pumps as two-pump unit (connection via Wilo Net)
– Cable break detection when using an analogue signal (in connection with 2 – 10 V or 4 – 20 mA)
– Outdoor installation with weather protection possible in accordance with the installation and operating instructions
– Pre-set date and time
– Thermal insulation shell for heating applications
Scope of delivery
– Pump
– Optimised Wilo-Connector the same for all sizes
– 2x threaded cable gland M16 x 1.5
– Washers for flange screws M12 and M16 (for nominal connection diameters DN 32 to DN 65)
– 2x gaskets for threaded connection
– Thermal insulation shell
– Concise Installation and operating instructions
Optional accessories:
– ClimaForm cold insulation to avoid the formation of condensate
– CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CANopen
– PT 1000 (B) pipe contact sensor (for domestic hot water)
– PT 1000 (AA) sensor for installation in immersion well
– Differential pressure sensor
Operating Data
Fluid media: Water 100 %
Fluid temperature: 20.00 °C
Requested flow:
Requested head:
Min. fluid temperature: -10 °C
Max. fluid temperature: 110 °C
Min. ambient temperature: -10 °C
Max. ambient temperature: 40 °C
Maximum operating pressure: 10 bar
Minimum suction head at 50 °C: 5 m
Minimum suction head at 95 °C: 12 m
Minimum suction head at 110 °C: 18 m
Motor data
Energy efficiency index (EEI): ≤ 0.17
Emitted interference: EN 61800-3;2004+A1;2012 /residential area (C1)
Interference resistance: EN 61800-3;2004+A1;2012 /industrial environment (C2)
Mains connection: 1~230V/50 Hz
Power consumption: 510 W
Min. speed: 650 1/min
Max. speed: 4,950 1/min
Protection class motor: IPX4D
Threaded cable connection: 5 x M16x1.5
Materials
Pump housing: 5.1301/EN-GJL-250
Impeller: PPS-GF40
Shaft: 1.4028, DLC-coated
Bearing: Carbon, antimony-impregnated
Installation dimensions
Pipe connection on the suction side: DN 32, PN 6/10
Pipe connection on the discharge side: DN 32, PN 6/10
Port-to-port length: 220 mm
Ordering information
Brand: Wilo
Product description: Stratos MAXO 32/0,5-16 PN6/10
Net weight, approx.: 15.4 kg
Article number: 2164581